GATE → 2026 → Power Systems → Generation, Transmission & Load Flow
In a power system with N buses (P generator buses, Q load buses), what is the size of the Jacobian matrix in the Newton-Raphson method?
(A) (B) (2N - 1 - P) x (2N - 1 - P)
(C) (D) GATE → 2026 → Power Systems → Generation, Transmission & Load Flow
For a transformer with voltage ratio V_p/V_s = 0.866 + j0.5 and leakage admittance y_t referred to secondary, what is the Y-bus matrix?
(A) [I_p; I_s] = [ y_t/(0.866+j0.5), -y_t/(0.866+j0.5); -y_t/(0.866+j0.5), y_t/(0.866+j0.5) ] [V_p; V_s]
(B) [I_p; I_s] = [ y_t, -y_t; -y_t, y_t ] [V_p; V_s]
(C) [I_p; I_s] = [ y_t, -y_t/(0.866+j0.5); -y_t/(0.866+j0.5), y_t ] [V_p; V_s]
(D) [I_p; I_s] = [ y_t, -y_t/(0.866-j0.5); -y_t/(0.866+j0.5), y_t ] [V_p; V_s]
GATE → 2026 → Power Systems → Generation, Transmission & Load Flow
For the balanced transmission line under Case-1 (Z = 0.75<0°) and Case-2 (Z = 0.75<90°), which statements regarding power losses are correct?
(A) Real power loss in Case-1 is more than that in Case-2
(B) Real power loss in Case-2 is more than that in Case-1
(C) Reactive power loss in Case-1 is more than that in Case-2
(D) Reactive power loss in Case-2 is more than that in Case-1
GATE → 2026 → Power Systems → Generation, Transmission & Load Flow
For economic load dispatch with given cost functions and loss formula, find the real power loss at optimal generation (Lambda = 70.25).
GATE → 2025 → Power Systems → Generation, Transmission & Load Flow
During power failure, a household UPS supplying power to lights and fans is represented in NR load-flow as a
GATE → 2025 → Power Systems → Generation, Transmission & Load Flow
For a distribution feeder with R/X = 5, find the load power factor at which maximum voltage drop occurs.
GATE → 2025 → Power Systems → Generation, Transmission & Load Flow
A 3-phase 4 kV induction motor draws 390 kVA at 0.77 pf lag. Shunt capacitors correct pf to 0.85 pf lag. Find capacitor bank line current in A.
GATE → 2025 → Power Systems → Generation, Transmission & Load Flow
Given incremental cost data for two generating units, find total plant output at incremental cost of 11,800 Rs/MWh without exceeding unit capacities.
GATE → 2024 → Power Systems → Generation, Transmission & Load Flow
For the 4-bus network with branch impedances 4z, z, 2z, 4z, which branch should be opened for minimum loss?
GATE → 2024 → Power Systems → Generation, Transmission & Load Flow
Using the incremental cost curves for Gen A and Gen B, find the common load in MW when incremental cost is Rs. 7400/MWh.
GATE → 2024 → Power Systems → Generation, Transmission & Load Flow
A synchronous generator supplies an inductive load (pf = sqrt(3)/2) through a line (X = 5 ohm). With X_s = 30 ohm at rated voltage and current, find the generator terminal power factor.
GATE → 2024 → Power Systems → Generation, Transmission & Load Flow
For the 3-bus lossless network with given reactances and P_1 = m P_2, if power flow from bus 1 to bus 2 is 0 pu, which condition holds?
GATE → 2024 → Power Systems → Generation, Transmission & Load Flow
Which options are correct regarding Automatic Generation Control (AGC) and Automatic Voltage Regulator (AVR)?
(A) AGC response has a local effect on frequency while AVR response has a global effect on voltage.
(B) AGC response has a global effect on frequency while AVR response has a local effect on voltage.
(C) AGC regulates the field current of the synchronous generator while AVR regulates the generator's mechanical power input.
(D) AGC regulates the generator's mechanical power input while AVR regulates the field current of the synchronous generator.
GATE → 2023 → Power Systems → Generation, Transmission & Load Flow
When parameter 'a' in the fuel cost function of unit 1 increases by 10% under economic dispatch, what happens to P_G1 and total cost F?
(A) P_G1 will decrease and F will increase
(B) Both P_G1 and F will increase
(C) P_G1 will increase and F will decrease
(D) Both P_G1 and F will decrease
GATE → 2023 → Power Systems → Generation, Transmission & Load Flow
Given the Y_bus matrix of a 3-bus power system with no shunt reactors, which statements can NOT be true regarding line charging and shunt capacitors?
(A) Line charging capacitor of finite value is present in all three lines
(B) Line charging capacitor of finite value is present in line 2-3 only
(C) Line charging capacitor of finite value is present in line 2-3 only and shunt capacitor of finite value is present in bus 1 only
(D) Line charging capacitor of finite value is present in line 2-3 only and shunt capacitor of finite value is present in bus 3 only
GATE → 2023 → Power Systems → Generation, Transmission & Load Flow
For a 400 km, 275 kV transmission line represented by nominal-pi model, find the phase angle difference delta for maximum active power delivery in degrees.
GATE → 2023 → Power Systems → Generation, Transmission & Load Flow
For the 3-bus power system with specified generation, infinite bus, and controlled current source, categorize buses 1, 2, and 3 for load flow analysis.
(A) Bus 1: Slack bus, Bus 2: PV bus, Bus 3: PQ bus
(B) Bus 1: PV bus, Bus 2: Slack bus, Bus 3: PV bus
(C) Bus 1: PQ bus, Bus 2: PQ bus, Bus 3: Slack bus
(D) Bus 1: PV bus, Bus 2: P-Q bus, Bus 3: Slack bus
GATE → 2023 → Power Systems → Generation, Transmission & Load Flow
For a balanced delta load supplied through line inductance L = 31.83 mH per phase from a 415 V source, find the magnitude of terminal voltage V_AB in volts.
GATE → 2022 → Power Systems → Generation, Transmission & Load Flow
Find the geometric mean radius (GMR) of a conductor having four equal strands of radius r arranged in a square bundle.
GATE → 2022 → Power Systems → Generation, Transmission & Load Flow
If 5% of the supplied power reaches the output of a cable, what is the power loss in decibels?
GATE → 2022 → Power Systems → Generation, Transmission & Load Flow
For two thermal power plants with given cost functions and incremental cost lambda = 8 Rs/MWh meeting 550 MW demand, find optimal P1 and P2.
GATE → 2022 → Power Systems → Generation, Transmission & Load Flow
Two generating units (250 MW, R=6% and 400 MW, R=6.4%) share a 500 MW load in parallel. Find the load shared by the 250 MW unit in MW.